Breather Valve w/ Flame Arrester
KSBGFI/GSFI TYPE
The model KSBGFI and KSGSFI pressure vacuum valves with flame arrester are an advanced design for vent to Pipe away applications. Designed manufactured and tested according to the API 2000 code, BS7244, and EN12874 / ISO 16852 these valves the latest technologies to provide protection against positive or vacuum over pressure and prevent air intake, evaporative losses of product and help to contain odorous and potentially explosive vapors
Model KSBGFI /GSFI, which is used for the protector of fluid storage tank, is composed of one body with the functions of pressure relief, vacuum relief, and to block the external repellent fire.
This is consist of the flame arrester which blocks the external repellent fire, the function of discharge the overpressure developed during intake air to the storage tank, and the function of intake the air under the constant pressure during unloading. And this is the safe valve to prevent the many kinds of storage tank from the deflation (vacuum), inflation ( pressure ) and fire.
The standard flame cell is suitable for NEC group D or IEC IIA gases, Cells for other gas groups are available as additional extras.
The KSBGFI is a weighted pallet model designed to handle pressure and vacuum with a minimum pressure of +/-20mmW.C and a maximum setting of +700/-430 mmW.C
The KSGSFI is a spring loaded model designed to handle pressure and vacuum with a minimum pressure of +/-700mmW.C and a maximum setting of +/- 9,000mmW.C.
Body materials are available in Aluminum, Carbon Steel, 304SS and 316SS with various trims to suit individual requirements.
Sizes range from 50mm through to 350mm with ANSI 150lb flanges as standard.